Parameters
TECHNICAL CHARACTERISTICS
| |
|
RT 5 |
RT 9 |
RT 15 |
RT 20 |
RT 30 |
| Thermal power max |
kW |
5 |
9 |
15 |
20 |
30 |
| min |
kW |
2.5 |
4.5 |
7.5 |
10 |
10 |
| Air flow rate |
m3/h |
480 |
720 |
1 300 |
2 600 / 1 900 |
2 600 / 1 900 |
| Sound level |
dBA |
40 |
44 |
47 |
60 / 52 |
60 / 52 |
| Air range (without heating) |
m |
11 |
12 |
15 |
19 |
19 |
| Electrical supply* |
|
3 x 400 V + N - 50 Hz |
| Current consumption |
A |
7.3 |
13.1 |
21.7 |
29.5 |
43.9 |
| Wire cross section |
|
For the cross section count 1 mm² for 7 amps |
| Width A |
mm |
335 |
405 |
450 |
478 |
478 |
| Height B |
mm |
255 |
315 |
520 |
576 |
576 |
| Depth C |
mm |
276 |
335 |
510 |
545 |
545 |
| Mass |
kg |
7 |
10 |
22 |
27 |
31 |
* A neutral is essential for the external supply of the fan (single phase 230 V)